Power Semiconductor Devices
Latest Post
Conventional three-phase six-step VSC
The conventional three-phase six-switch VSC is shown in Figure 6.32. It consists of six switches S1-S6 and six antiparallel diodes D1-D6. The number indicates their order of being turned on. A fictitious neutral (o) as a mid-point is also included although in most cases is not available. However, when the converter under consideration is used as an active filter in the case of a four-wire three-phase system, this point (o) is used to connect the fourth-wire. This case will be discussed further in later parts.
The three converter legs are controlled with a phase-shift of 120o between them. The basic way to control the three-phase six-switch VSC is to turn on each switch for half of the period (1800) with a sequence 1, 2, 3, . . . as they are numbered and shown in Figure 6.32.
Fig. 6.32 Conventional three-phase six-switch VSC.
The operation of the converter can be explained with the assistance of Figure 6.33. Specifically, the control signals for each of the six switches are shown in Figure 6.33(a). Clearly, each switch remains on for 1800 and every 600 a new switch is turned on and one of the previous group is turned off. At any given time therefore, one switch of each leg is on. Assuming that the fictitious mid-point (0) is available, three square-type waveforms for the voltages vAO, vBO, and vCO can be drawn as shown in Figure 6.33(b). Each of the voltage waveforms has two peak values of Vdc/2, and -Vdc/2, and they are displaced by 120o from each other.
From the three waveforms vAO, vBO, and vCO, the line-to-line voltage waveforms can be drawn since
The three resultant line-to-line voltage waveforms are then shown in Figure 6.33(c). It is clear that each waveform takes three values (Vdc, 0, -Vdc) and there is a 120o phase-shift between them. These waveforms have a 60o interval when they are zero for each half of the period, a total of 120o per period. As explained earlier, each leg can handle current in both directions at any time, since either the turned on switch or the antiparallel diode of the other switch can be the conducting element depending upon the polarity of the output line current.
The potential of the load neutral point (n) shown in Figure 6.32 with respect to the mid-point of the DC bus (0) is drawn in Figure 6.33(d). It can be seen that such a waveform has frequency three times the output frequency and the two peak values are between Vdc/6 and -Vdc/6. Finally, the line-to-load neutral point (n) voltage waveform is illustrated in Figure 6.33(e). Such a voltage waveform has two positive values (Vdc/3 and 2Vdc/3) and two negative ones (-Vdc/3 and -2Vdc/3).
Fig. 6.33 Key waveforms of the three-phase six-step VSC circuit operation. (a) control signals for switches S1, S2, S3, S4 ,S5 , S6; (b) voltage waveforms vAO, vBO, and vCO; (c) output line-to-line voltage waveforms vAB, vBC, vCA ; (d) voltage waveform between the load neutral point (n) and the DC bus mid-point (0); (e) voltage waveform between the line point A and the load neutral point n; (f) harmonic spectrum of the line-to-DC bus mid-point; and (g) harmonic spectrum of the line-to-line voltage vAB.
The harmonics of the various waveforms can be calculated using Fourier series. The fundamental amplitude of the voltage waveforms vAO, vBO, and vCO is
where h is the order of the harmonic.
For the line-to-line voltage waveforms vAB, vBC, and vCA then the fundamental amplitude is
and therefore the rms value of the fundamental component is then
Similarly, the amplitude of the harmonic voltages is
The rms value of the line-to-line voltage including all harmonics is
The normalized spectrum of the line-to-DC bus mid-point and the line-to-line voltage waveforms are plotted in Figures 6.33(f) and (g) respectively. It can be seen that the voltage waveforms vAO, vBO, and vCO contain all odd harmonics. The load connection as shown in Figure 6.32 does not allow 3rd harmonic and all multiples to flow, and this is confirmed with the spectrum of the line-to-line voltage waveform vAB where 3rd, 9th and 15th harmonics are eliminated as shown in Figure 6.33(g).
previous Single-phase full-bridge VSC
next Single-phase half-bridge neutral-point-clamped (NPC) vSC
Single-phase full-bridge VSC
In this section we will examine in detail the single-phase full-bridge VSC. Its power circuit is shown in Figure 6.26. It consists of two identical legs like the half-bridge single-phase converter (Figure 6.23) discussed in Section 6.3.1. Specifically, there are four switching elements (S1, S2, S3, S4), four antiparallel diodes (D1, D2, D3, D4) and a DC bus voltage source Vdc that can be a single capacitor. The other leg provides the return path for the current this time and the DC bus mid-point does not need to be available to connect the load. The output voltage v0 appears across the two points A and B as shown in Figure 6.26.
The control restriction discussed for the single-phase half-bridge topology (Figure 6.23) applies to this converter as well. Clearly the control signals for the switch pairs (S1, S2) and (S3, S4) must be complementary to avoid any bridge destruction due to shoot through of infinite current (at least theoretically).
There are two control methods for this topology. The first one treats the switches (S1, S4) and (S2, S3) as a pair. This means that they are turned on and off at the same time and for the same duration. For square-wave operation the switches S1 and S4 are on for half of the period. For the other half, the pair of S2, S3 is turned on. Like the single-phase half-bridge VSC, the direction of the output current i0 determines the conduction state of each semiconductor.
When the two switches S1 and S4 are turned on, the voltage at the output is equal to the DC bus voltage Vdc. Similarly, when the switches S2 and S3 are turned on the output voltage is equal to - Vdc. Such circuit operation is illustrated in Figure 6.27.
In the first case, when the direction of the output current io is positive as shown in Figure 6.26, the current flows through switches S1 and S4 and the power is transferred from the DC side to the AC one (t4 < t < t5). When the current becomes negative, although the switches S1 and S4 are turned on, the diodes D1 and D4 conduct the current and return power back to the DC bus from the AC side (t3 < t < t4). For the other half of the period, when the switches S2 and S3 are turned on and the current is positive, the diodes D2 and D3 conduct (t1 < t < t2). In this
Fig. 6.26 Single-phase full-bridge VSC.
Fig. 6.27 Key waveforms of the single-phase full-bridge VSC circuit operation. (a) output voltage V0 = VAB; (b) output current i0; (c) input DC bus current id; (d) harmonic spectrum of the output voltage V0 = VAB; (e) harmonic spectrum of the output current i0; and (f) harmonic spectrum of the input DC bus current id.
instance, power is transferred also back to the DC side from the AC side. Finally, when the current is negative, the switches S2 and S3 carry the current and assist the converter to transfer power from the DC bus to the AC side (t2 < t < t3). In summary, there are four distinct modes of operation for this converter when the control method shown in Figure 6.27 is employed (two inverter modes and two rectifier modes). Simply said, at all times two switches are turned on and the legs are controlled in a synchronized way.
The output voltage v0 = vAB is shown in Figure 6.27(a). The output current i0 and the input DC current id are also plotted in Figures 6.27(b) and (c) respectively. Similarly, like the case of the half-bridge topology, the square-wave generated across the AC side includes all odd harmonics and being a single-phase system, the third harmonic is also present (Figure 6.27(d)). These harmonics when reflected back to the DC side source include all even harmonics (Figure 6.27(f).
Fig. 6.28 Quadrants of operation of the single-phase full-bridge VSC.
The fundamental component of the output voltage v0 waveform has an amplitude value of
(6.20)
And its various harmonics are given by
where h is the order of the harmonic.
The converter is capable of operating in all four quadrants of voltage and current as shown in Figure 6.28. The various modes and their relationship to the switching and/or conduction state of the semiconductors are also summarized in Table 6.4 for further clarity. The phase relationship between the AC output voltage and AC output current does not have to be fixed and the converter can provide real and reactive power at all leading and lagging power factors. However, the converter itself cannot control the output voltage if the DC bus voltage Vdc remains constant. There is a need to adjust the level of the DC bus voltage if one wants to control the rms value of the output voltage v0.
There is however a way to control the rms value of the fundamental component of the output voltage as well as the harmonic content of the fixed waveform shown in Figure 6.27(a). In this method, the control signals of the two legs are not
Table 6.4 Modes of operation of the single-phase full-bridge VSC
synchronized in any way and the switches are not treated as pairs like previously. For the safe operation of the converter, the control signals between (S1 and S2) and (S3 and S4) must be complementary. In this case, there is a phase- shift between the two legs and this way a zero volts interval can appear across the output.
For instance, if switches S1 and S3 are turned on at the same time, the output voltage (vAB) will be zero. The current in the case of other than unity power factor must keep flowing. There is no power exchange between the DC side and the AC one (free-wheeling mode). If the current is positive, the current flows through S1 and D3. If the current is negative, it flows through D1 and S3. Similarly, when the two bottom switches S2 and S4 are turned on at the same time, the output voltage (vAB) is zero and the output current once again determines which element conducts and allows the output current to continue flowing. Specifically, if the current is positive, the diode D2 and the switch S4 are conducting. In the case that the current is negative, the switch S2 and diode D4 provide a path for the output current. These extra modes of operation for the single-phase full-bridge topology (Figure 6.26) are also included in Table 6.4 as the free-wheeling modes.
For a given phase-shift (a degrees) between the control signals of the two legs, the waveforms are shown in Figure 6.29. It is clear that the output voltage waveform is a three-level one, being able to have the values of Vdc, 0 and -Vdc as shown in Figure 6.29(a). The control signals are shown in Figures 6.29(b)-(d). It is also clear that between the top and bottom switches of each leg complementary control signals are used. It should be noted that for α = 0, the output voltage becomes similar to the previously presented control method (square-wave, Figure 6.27(a)).
The output voltage vo (vAB) is shown in Figure 6.30(a) along with the output current io and the DC bus current id in Figures 6.30(b) and (c) respectively. Therefore, by controlling the phase-shift between the two legs (α degrees), the rms value of the fundamental component can be controlled. The amplitude of all odd harmonics, as shown in Figure 6.30(d) for the output voltage, can also be controlled. The output current has only a fundamental component as shown in Figure 6.30(e), where the DC bus current has a DC component and all even harmonics as shown in Figure 6.30(f).
Fig. 6.29 Key waveforms of the single-phase full-bridge phase-shifted controlled VSC circuit operation. (a) output voltage vo = vAB; (b) control signal for switch S1 ; (c) control signal for switch S2; (d) control signal for switch S3; and (e) control signal for switch S4.
Fig. 6.30 Key waveforms of the single-phase full-bridge phase-shifted controlled VSC circuit operation. (a) output voltage vo = vAB; (b) output current io; (c) DC bus current id; (d) harmonic spectrum of the output voltage vo = vAB; (e) harmonic spectrum of the output current io; and (f) harmonic spectrum of the input DC bus current id.
Fig. 6.31 Normalized amplitudes of fundamental and harmonics for the phase-shifted output voltage as a function of α (zero volts interval in degrees).
For a given zero interval α in degrees, as shown in Figures 6.29(a) and 6.30(a), the amplitude of the fundamental and harmonics are as follows
where h is the order of the harmonic.
When α = 0 the converter operates as a square-wave one (Figure 6.27). The normalized amplitude of the fundamental and the most significant harmonics, i.e. 3rd, 5th, 7th and 9th to the output of the square-wave converter as a function of α, are plotted in Figure 6.31.
previous Single-phase half-bridge VSC
next Conventional three-phase six-step VSC
Single-phase half-bridge VSC
Voltage-source converters (VSCs) and derived controllers
- Voltage-source converters or else voltage-source inverters (VSIs): the DC bus input is a voltage source (typically a capacitor) and its current through can be either positive or negative. This allows power flow between the DC and AC sides to be bidirectional through the reversal of the direction of the current.
- Current-source converters (CSCs) or else current-source inverters (CSIs): the DC bus input is a current source (typically an inductor in series with a voltage source, i.e. a capacitor) and its voltage across can be either positive or negative. This also allows the power flow between the DC and AC sides to be bidirectional through the reversal of the polarity of the voltage.
Switching transients in the general case
The current has a fundamental-frequency component iAC which leads the supply voltage by π/2 radians. Its amplitude îAC is given by
Switching transients and the concept of transient-free switching
The thyristor-switched capacitor (TSC)
The thyristor-controlled transformer (TCT)
next The thyristor-switched capacitor (TSC)
Thyristor-controlled equipment
| Harmonic order | Percentage |
| 1 | 100.00 |
| 3 | (13.78)b |
| 5 | 5.05 |
| 7 | 2.59 |
| 9 | (1.57) |
| 11 | 1.05 |
| 13 | 0.75 |
| 15 | (0.57) |
| 17 | 0.44 |
| 19 | 0.35 |
| 21 | (0.29) |
| 23 | 0.24 |
| 25 | 0.20 |
| 27 | (0.17) |
| 29 | 0.15 |
| 31 | 0.13 |
| 33 | (0.12) |
| 35 | 0.10 |
| 37 | 0.09 |
b The values apply to both phase and line currents, except that triples harmonics do not appear in the line currents. Balanced conditions are assumed.
With both 6-pulse and 12-pulse TCR compensators, the need for filters and their frequency responses must be evaluated with due regard to the possibility of unbalanced operation. The influence of other capacitor balks and sources of harmonic currents in the electrical neighbourhood of the compensator must also be taken into account. For this purpose, several software packages are available and some examples with a specific one will be provided later.
The 12-pulse connection has the further advantage that if one half is faulted the other may be able to continue to operate normally. The control system must take into account the 30° phase shift between the two TCRs, and must be designed to ensure accurate harmonic cancellation. A variant of the 12-pulse TCR uses two separate transformers instead of one with two secondaries.